SMT2200 - APC Smart-UPS 2200VA LCD 120V. View the new All Products menu. APC Smart-UPS 2200VA LCD 120V. Includes: CD with software, Documentation CD, Smart UPS signalling RS-232 cable, USB cable. FCC part 15 approval for Smart-UPS 2200/3000 VA LCD 120V (Version 0) Add to My Documents. FCC part 15 approval for Smart-UPS 2200. APC Smart-UPS 2200VA LCD RM 2U 230V. Includes: CD with software, Documentation CD, Installation guide, Rack Mounting support rails, Rack mounting hardware, Smart UPS signalling RS-232 cable, USB cable. Installation Smart-UPS SMT 750/1000/1500/2200/3000 VA 120/230 Vac, 500 VA 100 Vac Rack-Mount 2U (Version 6) Add to My Documents. Smart-UPS XL 2200VA - read user manual online or download in PDF format. Pages in total: 22. Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower 1 Overview Product Description The APC® by Schneider Electric Smart-UPS® 500 VA to 3000 VA Tower is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power. Smart-UPS X-Series 2000/2200/3000 VA Operation i. The user manual is also available on the APC Web site at www.apc.com. External Battery Pack. For installation information, see the Smart-UPS X 2000-3000 VA External Battery Pack Installation guide that is included with the external battery pack. The guide is. User Manual English APC Smart-UPS® 2200 VA 120/230 Vac 3000 VA 100/120/208/230 Vac 2U Rack Mount Uninterruptible Power Supply. 1 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags, and surges from reaching your equipment. The uninterruptible power supply (UPS) filters small util.
16
Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual
Troubleshooting
Troubleshooting
Use this table to solve minor UPS installation and operation problems. Refer to www.apc.com for assistance
with complex UPS problems.
Problem and/or Possible Cause
Solution
UPS will not turn on
The battery is not connected properly.
Check that the battery connector is fully engaged.
Test
button not pushed.
Press the
Test button once to power-up the UPS and connected equipment.
The UPS is not connected to utility
power supply.
Check that the power cable from the UPS to the utility power supply is
securely connected at both ends.
Very low or no utility voltage.
Check the utility power supply to the UPS by plugging in a table lamp. If the
light is very dim, have the utility voltage checked.
UPS will not turn off
The UPS is experiencing an internal
fault.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
UPS beeps occasionally
Normal UPS operation when running
on battery.
None: The UPS is protecting the connected equipment.
Press the Test button to silence this alarm.
UPS is not providing expected backup time
The UPS battery(s) are weak due to a
recent power outage or battery(s) are
near the end of their service life.
Charge the battery(s). Batteries require recharging after extended outages.
Batteries can wear faster when put into service often or when operated at
elevated temperatures. If the battery(s) are near the end of their service life,
consider replacing the battery(s) even if the Replace Battery LED is not yet
illuminated.
All LEDs are illuminated and the UPS emits a constant beeping
The UPS is experiencing an internal
fault.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
Front panel LEDs flash sequentially
The UPS has been shut down remotely
through software or an optional
accessory card.
None: The UPS will restart automatically when utility power returns.
A
ll LEDs are off and the UPS is plugged into a wall outlet
The UPS is shut down or the battery is
discharged from an extended outage.
None: The UPS will restart automatically when utility power is restored and
the battery has a sufficient charge.
Initial
To obtain warranty coverage, please fill out and return the warranty registration card now.
Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.
Placement
Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Do not operate the UPS where the temperature and humidity is outside the specified limits.
Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the warranty.
Installation
To install this UPS, please follow the installation instructions in the
This UPS is equipped with a SmartSlot for accessories. See the APC Website (www.apcc.com) for available accessories.
Charge the battery
The UPS charges its battery whenever it is connected to utility power. The battery will charge fully during the first 4 hours of normal operation. Do not expect full runtime during this initial charge period.
Operating Instructions
Switch On — Switch Off
With the UPS plugged in, press and release the large upper on/test button to supply power to the loads. The
loads are immediately powered while the UPS performs a
Press and release the small, lower off button to turn off power to the loads. It may be convenient to use the UPS as a master on/off switch for the protected equipment.
Note: Whenever the UPS is plugged in and utility voltage is present, the charger maintains battery charge.
The
The UPS performs a
During the
If the UPS fails the
The loads are not affected by a failed test. Recharge the battery overnight and perform the
SmartTrim
The SmartTrim LED comes on to indicate that the UPS is compensating for a high voltage.
SmartBoost
The SmartBoost LED comes on to indicate that the UPS is compensating for a low voltage.
APC
Uninterruptible Power Supply
230 VAC User’s Manual
Rear Views
2200 and 3000 VA | 1000 and 1400 VA | 450 and 700 VA |
Connect Computer Interface Port (Optional)
Power management software and interface kits can be used with this UPS. Use only kits supplied or approved by the manufacturer. If used, connect the interface cable to the
Connect Ground Leads to TVSS Connector (Optional)
The UPS features a TVSS connector for connecting the ground lead on transient voltage
Battery Pack Connector (3000 VA only)
Use the battery pack connector to connect the optional external battery pack.
On Battery
During
Low Battery
When the UPS is operating
100% | Battery Charge Bar Graph |
80% | The |
60% | shows the present charge of the UPS’s battery as a |
percentage of the battery’s capacity. When all five | |
40% | |
LEDs light, the battery is fully charged. The top | |
20% | LED goes out whenever the battery is not 100% |
charged. When the LEDs are flashing, the battery |
can supply less than the “low battery warning interval” time for the load.
Shutdown Mode
If there is no utility power present, a host system connected to the computer interface port can command the UPS to shut down. This is normally done to preserve battery capacity after a controlled shutdown of the protected system. In shutdown mode the UPS stops supplying power to the load, waiting for the return of utility power.
The UPS scrolls the front panel indicators sequentially in shutdown mode. If the UPS has shutdown due to a low battery, the UPS lights the Battery Charge Bar Graph only. When line power is restored, the UPS returns to
Replace Battery
If the battery fails a
85% | Load Bar Graph |
67% | The |
50% | shows the power drawn from the UPS by the load. |
The display indicates the percentage of the UPS’s | |
33% | |
rated capacity. For example, if three LEDs are lit, the | |
17% | |
load is drawing between 50% and 67% of the UPS’s | |
capacity. If all five LEDs light, thoroughly test your | |
complete system to make sure that the UPS will not | |
become overloaded. |
Voltage Sensitivity
The UPS detects line voltage distortions such as spikes, notches, dips, and swells, as well as distortions caused by operation with inexpensive
To reduce UPS sensitivity, press the configuration button on the rear panel. Use a pointed object such as a pen to press the button. Press it once to set the UPS’s sensitivity toreduced. Press it again to set the sensitivity tolow. Press the button a third time to
reset normal sensitivity.
normal
reduced | When the UPS is set to normal sensitivity, the |
configuration LED is brightly lit. When it is set to | |
low | |
reduced sensitivity, the LED is dimly lit. When it is | |
set to low sensitivity, the LED is off. |
•Press and hold the on/test button until the UPS begins beeping.
•Release the on/test button during the beeping to start the UPS.
Utility Voltage Bar Graph
196 | If no LEDs come on and the UPS is plugged into a | |
working AC power outlet, the line voltage is extremely | ||
264 | ||
low. If all five LEDs come on, the line voltage is | ||
extremely high and should be checked by an electrician. | ||
The display indicates that the voltage is between the | ||
247 | displayed value from the list and the next higher value. | |
230 | For example, with three LEDs lit, the input voltage is | |
213 | between 230 and 247 VAC. |
Note: The UPS starts a
Storage
Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery fully charged. Before storing, charge the UPS for at least 4 hours. Disconnect any cables connected to the computer interface port to avoid unnecessarily draining the battery.
Extended storage
•At
•At +30 to +45 °C (+86 to +113 °F), charge the UPS’s battery every 3 months.
Replacing the Battery
This UPS has an easy to replace
Note: Please read the cautions in the APC Safety Guide.
Once the battery is disconnected, the loads are not protected from power outages.
Battery Replacement Procedure - 2200 - 3000 VA Models
1. Grasp the top edge of the bottom front cover and tilt it out.
2.Unhook the bottom section of the front cover from the chassis and set it aside.
3.Use a
open the door.
4. Grip the wires for the front set of batteries and pull firmly to disconnect the connector from the battery compartment. Remove the batteries.
5.Pull the white cord on the front battery connector to remove the batteries.
6.Set aside the foam spacer located between the batteries.
7.Reach into the battery compartment and grasp the white cord on the other battery connector. Pull firmly to disconnect the connector and remove the second set of
batteries.
Note: Be careful removing the batteries - they are heavy.
8.Slide the first set of new batteries into the unit. Hold the connector down below the top of the batteries and toward the door, otherwise the assembly will not fit. Guide the connector over the top of the batteries and press firmly to connect it to the rear connector of the battery compartment.
9.Set the foam spacer against the rear batteries to prevent the wires from being pinched.
Note: Small sparks at the battery connectors are normal during connection.
10.Slide the second set of batteries in, then guide the connector over the batteries and press firmly to connect it to the front connector of the battery compartment.
11.Now close the battery door, replace the screws, and replace the lower front cover.
12.Dispose of the old battery properly at an appropriate recycling facility or return it to the supplier in the packing material for the new battery. See the new battery instructions for more information.
Battery Replacement Procedure - 450 - 1400 VA Models
1. Grasp the top of the front cover and tilt it out and down.
2.Unhook the bottom of the cover from the chassis and lift it upward to expose the battery door. Be careful not to strain the ribbon cable. Do not touch the exposed
printed circuit board.
3. Fold the front cover on top of the UPS as shown.
4. Use a
Grasp the tab and gently pull the battery out of the UPS. 5. Disconnect the battery leads.
Apc Smart-ups 2200 Manual Diagram
•For the 450 through 1000 VA models, loosen the connectors by gently wiggling them while pulling straight back from the battery connector.
• For the 1400 VA model, pull the two gray couplers apart to disconnect the battery.
6. Connect the battery leads to the new battery.
Apc Smart Ups 2200 2u Manual
1400 VA | Note: Small sparks at the battery connectors are normal during connection. |
• For the 450 through 1000 VA models, connect the red wire to the positive (+) | |
terminal and the black wire to the negative | |
450 - 1000 VA | • For the 1400 VA model, connect the gray battery coupler to the UPS’s coupler. |
7. Now slide the battery into the UPS,close the battery door,replace the battery |
compartment screws, and replace the front cover.
8. Dispose of the old battery properly at an appropriate recycling facility or return it to the supplier in the packing material for the new battery. See the new battery instructions for more information.
Though it recognized our synced drive, it kept crashing even after trying to create a new folder. Your mileage may vary depending on the compatibility of your Android device and the version of your operating system. Acronis' other syncing and cloud features may sound great but its strongest asset lies in the the program's default disk backup and cloning functions; they're speedy and effective. We recommend that you exercise caution when using other recovery options, especially if you have other backup programs installed, as Acronis uses its own unique format. For our device, it flat out did not work as intended.
Place | Date | Stephen A. Lee, Regulatory Compliance Engineer | ||
Galway, Ireland | 1/1/97 | |||
Place | Date | |||
Gerard | Rutten, Managing Director, Europe |
User Configuration Items
Note: Setting these items requires optional software or hardware.
Function | Factory | User Selectable Choices | Description |
Default | |||
Automatic | Every 14 days | Every 7 days (168 hours), | Sets the interval at which the UPS |
(336 hours) | On Startup Only, No Self- | will execute a | |
Test | |||
UPS ID | UPS_IDEN | Up to eight characters to | Use this field to uniquely identify the |
define the UPS. | UPS for network management | ||
purposes. | |||
Date of Last Battery | Manufacture | Date of Battery | Reset this date on battery |
Replacement | Date | Replacement | replacement. |
Minimum Capacity Before | 0 percent | 15, 50, 90 percent | The UPS will charge its batteries to |
Return from Shutdown | the specified percentage before return | ||
from a shutdown. | |||
Sensitivity | Normal | Reduced, Low | Set lower than normal sensitivity to |
avoid lowered battery capacity and | |||
service life in situations where the | |||
load can tolerate minor power | |||
disturbances. | |||
Duration of Low Battery | 2 minutes | 5, 7, 10 minutes | Sets the time before shutdown at |
Warning | which the UPS issues a low battery | ||
warning. Set higher than the default | |||
only if the OS needs the time for | |||
graceful shutdown. | |||
Alarm Delay After Line Fail | 5 second delay | 30 second delay, At Low | To avoid alarms for minor power |
Battery Condition, No | glitches, set the alarm delay. | ||
Alarm | |||
Shutdown Delay | 20 seconds | 180, 300, 600 seconds | Sets the interval between when the |
UPS receives a shutdown command | |||
and when shutdown occurs. | |||
Synchronized | 0 seconds | 60, 180, 300 seconds | To avoid branch circuit overload, |
the UPS will wait the specified time | |||
after the return of utility power before | |||
Output Voltage | 230 Vac | 220, 225, 240 VAC | Sets the output voltage for |
operation. | |||
High Transfer Point | 253 Vac | 264, 271, 280 VAC | To avoid unnecessary battery usage, |
set the High Transfer Point higher if | |||
the utility voltage is chronically high | |||
and the load is known to work well | |||
under this condition. | |||
Low Transfer Point | 196 Vac | 188, 204, 208 VAC | Set the Low Transfer Point lower if |
the utility voltage is chronically low | |||
and the load can tolerate this | |||
condition. |
Apc Smart Ups Rt 2200 Manual Pdf
Service
If the UPS requires service do not return it to the dealer!
Apc Smart Ups 2200 Rack Mount Manual
Follow these steps:
1.Use the Troubleshooting section of theQuick Reference Guide to eliminate common problems.
2.Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common UPS problem!
3.If the problem persists, call customer service or visit the APC Internet Website (www.apcc.com).
•Note the model number of the UPS, the serial number, and the date purchased. A technician will ask you to describe the problem and try to solve it over the phone, if possible. If this is not possible the technician will issue a Return Merchandise Authorization Number (RMA#).
•If the UPS is under warranty, repairs are free. If not, there is a repair charge.
4.Pack the UPS in its original packaging. If the original packing is not available, ask customer service about obtaining a new set.
•Pack the UPS properly to avoid damage in transit. Never use Styrofoam beads for packaging. Damage sustained in transit is not covered under warranty.
•Include a letter with your name, RMA#, address, copy of the sales receipt, description of the trouble, your daytime phone number, and a check (if necessary).
5.Mark the RMA# on the outside of the package
6.Return the UPS by insured, prepaid carrier to the address given to you by Customer Service.
North & Latin America | Europe |
APC | APC |
132 Fairgrounds Road | Ballybritt Business Park |
West Kingston, Rhode Island 02892 USA | Galway, Ireland |
Internet: http://www.apcc.com | |
Regulatory Agency Approvals
B
N 3 9 M E6 1
Specifications
450 VA | 700 VA | 1000 VA | 1400 VA | 2200 VA | 3000 VA | ||||
Acceptable input voltage | 0 - 325 VAC | ||||||||
Output voltage | |||||||||
Input Protection | Resettable circuit breaker | ||||||||
Frequency limits | 50 or 60 Hz, ±5% | ||||||||
Transfer time | 2 ms typical, 4 ms maximum | ||||||||
Maximum load | 450 VA | 700 VA | 1000 VA | 1400 VA | 2200 VA | 3000 VA | |||
280 W | 450 W | 670 W | 950 W | 1600 W | 2250 W | ||||
220, 225, 230, or 240 VAC | |||||||||
50 or 60 Hz, ±0.1 Hz; unless synchronized to utility during brownout. | |||||||||
Protection | Overcurrent and | ||||||||
Noise Filter | Normal and common mode EMI/RFI suppression, 100 kHz to 10 MHz | ||||||||
Battery type | Spill proof, maintenance free, sealed | ||||||||
Typical battery life | 3 to 6 years, depending on number of discharge cycles and ambient temperature | ||||||||
Typical recharge time | 2 to 5 hours from total discharge | ||||||||
Operating temperature | 0 to +40 ºC (+32 to +104 ºF) | ||||||||
Storage temperature | |||||||||
Operating and storage relative | 0 to 95%, | ||||||||
humidity | |||||||||
Operating elevation | 0 to +3,000 m (0 to +10,000 ft) | ||||||||
Storage elevation | 0 to +15,000 m (0 to +50,000 ft) | ||||||||
Electromagnetic immunity | IEC | ||||||||
Audible noise in dBA at 1 m (3 ft) | <41 | <42 | <45 | <53 | |||||
Size (H x W x D) | 15.8 x 13.7 x 35.8 cm | 21.6 x 17 x 43.9 cm (8.5 x | 43.2 x 19.6 x 54.6 cm (17.0 | ||||||
(6.2 x 5.4 x 14.1 in.) | 6.7 x 17.3 in.) | x 7.7 x 21.5 in.) | |||||||
Weight - net (shipping) | 10.5 | 13.1 | 18.8 | 24.1 (26.1) | 51 (60.8) kg | 55.8 (64.4) | |||
(11.8) | (14.5) | (20.8) kg | kg | 112 (134) | kg | ||||
kg | kg | 41.5 (46) | 53 (58) lb. | lb. | 123 (142) | ||||
23.2 | 29 (32) | lb. | lb. | ||||||
(26) lb. | lb. | ||||||||
Safety approvals | GS licensed by VDE to EN 50091 and 60950 | ||||||||
EMC verification | CISPR 22 Class A |